KAYDON FILTRATION

LAGRANGE,  GA 
United States
  • Booth: 2949


Visit #2949 for oil conditioning /fuel purification needs.

Filtration Group’s Kaydon Filtration designs and builds oil and fuel filtration for the Power Generation market, with special expertise in turbine oil conditioning and diesel fuel purification.  Filtration Group’s Hydraulics family of businesses also includes FG Fluid Solutions, Zinga, and Air System Products.

Brands: TURBO-TOC turbine oil conditioning steam turbines Coalescer fuel conditioning diesel fuel combustion hydroelectric Vacuum dehydrators filtration varnish removal housings vessels


 Products

  • TURBO-TOC KLP Series
    The KLP TURBO-TOC turbine oil conditioning system's portability provides oil conditioning for a selected oil reservoir during equipment uptime and adds additional benefit during shutdown by quickly preparing the turbine oil for equipment start-up....

  • TURBO-TOC® turbine oil conditioning systems support long-term turbine operation and significantly reduce the probability of failures or unscheduled maintenance due to contaminated turbine oil.

    A major factor in turbine oil reliability is the control and removal of undesired particulate and water. When contamination
    invades turbine oil, protection of the turbine bearing and journal surfaces are placed at risk and turbine performance
    is jeopardized.

    The KLP TURBO-TOC turbine oil conditioning system's portability provides as needed oil conditioning for a selected
    oil reservoir during equipment uptime, and adds additional benefit during shutdown by quickly preparing the turbine
    oil for equipment start-up. After the system has removed the water from the turbine oil, it will accumulate in the
    coalescer vessel. When it has accumulated to a preset level, the automatic water drain will discharge the water from
    the system.

    The KLP series is equipped with a prefilter vessel containing a pleated, multi-layered micro-fiberglass filter for ultrafine
    particle removal and long element life. Particulate filtration is rated at Beta (5.1)=1000 per ISO 16889. An installation
    kit including one suction hose (10'), discharge hose (10'), and power cable (15') is provided with each KLP
    system.

    The KLP Series uses the same filter media and technology as the proven KL Series TURBO-TOC Turbine Oil Conditioners
    and is capable of meeting ISO Cleanliness Code 15/13/11. The KLP Series may be installed on a single
    reservoir or moved between multiple turbine oil reservoirs.

    Features: 

    • Portability allows the system to be shared between multiple turbine oil reservoirs
    • Contributes to dependable turbine operations and helps reduce turbine rotating component failures
    • Differential Pressure Gauge designed to monitor restriction of flow caused by contaminants and indicates remaining coalescer and separator element life
    • Sample port included to take bottle samples for oil quality analysis
    • Automatic air valve release allows for removal of trapped air
    • Sight glass provides visual indication of the accumulated water separated from turbine oil
    • Automatic water drain removes separated water
    Specifications and Details
    Available Flow Rates 3 gpm or 5 gpm
    Sizing Up to 600 gallons
    System Pressure 100 PSIG / 7 BAR (maximum)
    Environmental Parameters

    Minimum Ambient Temperature: 32 F (0 C)
    Maximum Ambient Temperature: 104 F (40 C)

    Operating Voltage 3 gpm; 120 VAC / 1 PH / 60 Hz / 10 amps
    3 gpm; 460 VAC / 3 PH / 60 Hz / 1.1 amps
    5 gpm: 460 VAC / 3 PH / 60 Hz / 2.1 amps
    Materials of Construction Metals: Carbon Steel
    Elastomers: Buna-N
    Paint: Epoxy (Kaydon Blue)
    Pressure Vessel Carbon Steel
    Inlet/Outlet Connections Type: NPT
    Inlet: 3/4 inch (19.05 mm)
    Outlet: 1/2 inch (12.7 mm)
    Pump/Motor Assembly Pump Type: gear - positive displacement
    3 gpm: 1/2 HP / 5 gpm: 3/4 HP
    Fluid Compatibility ISO 32, ISO 46, and ISO 68 mineral base
    turbine oil
    Filter Stages 1st Stage: 30 mesh pump protection strainer
    2nd Stage: particulate removal
    3rd Stage: water removal
    Performance Particulate: ISO Cleanliness Code 15/13/111
    Water: removal to less than 100 ppm 
    Weight (approximate) 400 lbs
    Dimensions (inches) 42.5 L x 27 W x 44 H

Send Email